Abstract
The increasing energy consumption and its consequences have led to a major need for energy saving measures. Therefore, the passive house concept has been introduced. Passive houses have a low heating demand, so that it is theoretically possible to simplify the space heating distribution system by for example reduce the number of radiators. It has therefore been investigated if one central heat source can give sufficient thermal comfort in a whole housing unit. Research shows, with the use of simulations for Belgian climate, that thermal comfort can be obtained in the whole dwelling if the internal doors are open. Thus, the air flows through these doors are central for the thermal comfort in passive houses. Different analytical models for the calculation of velocity and volume flows through large vertical openings are therefore presented and compared. These models, and thus the simulations are based on a set of assumptions which are assessed. Measurements were conducted to investigate if the assumptions are valid and if thermal comfort can be achieved in a real situation. First, laboratory measurements were conducted to see if the planned setup functioned. Then measurements were conducted in an actual passive house; velocity and temperature were measured in a doorway and the air and surface temperatures were measured on both sides of the aperture. Three different heat sources were used and placed in four different positions where one position was on the first floor. There were several factors in the passive house that can have affected the results; the measurements were done in a staircase, a frame was built around the stairs and the measurement equipment all had margins of error. The measurements gave a velocity profile which deviated some from the theory. While investigating this it was found that many of the central assumptions were invalid. The temperatures in the thermal zones were neither uniform nor with small and similar temperature gradients; the temperatures varied in both zones and the thermal gradients differed for the two rooms and could not be considered small. The results imply that there is heat transfer between the two air streams in the aperture which contradicts the assumption of this not being the case. The passive house also has a ventilation system while the theoretical models assume that there is no supply of ventilation air. The consequence of these assumptions being invalid is that the velocity profile is changed from a symmetric, parabolic shape to a non-symmetric, non-parabolic shape. The position of the neutral plane was also found to be affected by the supplied ventilation air rate. One central assumption was found to be valid; the results showed that there was one neutral plane in the middle of the aperture. The volume flows were calculated based on the measured velocities and neither the velocities nor the volume flows was equal to the analytical calculated values. Thus, it is concluded that the analytical models cannot be used to find exact values for velocity and volume flows. However, the majority of the models can be used to find indications for these magnitudes, especially for the volume flows. The discharge coefficient Cd was found to be varying so that one value cannot be used for all cases. The deviations from the theory were more evident for the cases with the heat sources located upstairs as the velocity profile and temperature distribution in the aperture differed from the other cases. The neutral plane was located higher up in the aperture and thus none of the central assumptions are valid. The theoretical models are therefore found inapplicable when the heat source is located above the aperture. Even though the measurement results do not match the theory completely there were no problems with the thermal comfort in the house during the measurement period. The settings for the heat sources are found to be important for the thermal comfort.
Thermal conductivity of TiO2 nanotubes prepared from a NaOH treatment of TiO2 particles with subsequent acid washing and annealing has been investigated. The obtained TiO2 nanotubes have a tetragonal anatase structure, and have a typical inner diameter of about 4-5 nm, wall thickness of about 2-3 nm, and length up to several hundred nanometers. TiO2 nanotubes show a significantly reduced thermal conductivity of about 0.40-0.84 W/(m·K) (average 0.62 W/(m.K)) at room temperature, as compared to about 8.5 W/(m·K) for the bulk TiO2 materials. The great suppression in thermal conductivity can be understood by means of increased phonon-boundary scattering and enhanced phonon confinement in TiO2 nanotubes with unique nanotubular morphology, small featured sizes, and large surface area (~258 m2/g). A theoretical analysis including the surface scattering and size confinement effects of phonon transport in TiO2 nanotubes is also reported, which results in an intrinsic thermal conductivity of 0.30-0.77 W/(m·K) (average 0.54 W/(m.K)) for individual TiO2 nanotubes with wall thickness of 2-3 nm, in harmony with the experimental values.
This thesis investigates whether the use of TMA is suitable for and of benefit to the Norwegian building industry.
Power House One plans to use the same heating technology as the Sparebank1 building in Trondheim. This building uses ventilation to distribute thermal energy to the end of activating the thermal mass. The purpose of this thesis was therefore to determine whether it is more efficient to use water rather than air to distribute thermal energy. Water has a higher volumetric heat capacity than air and therefore water-carrying pipes embedded in the thermal mass should be more efficient in distributing thermal energy. This thesis found that integrating thermal mass activation into building design is a valuable means to improve the thermal comfort of an indoor space. While its performance for improving thermal comfort is better than that of ventilation, there is no clear answer as to whether TMA is also more energy efficient than activating this same thermal mass using ventilation heat. Further research is thus necessary to investigate this issue.
Illustration: Powerhouse 1, Snøhetta
Shading systems are widely used, also in Nordic climates, in conjunction with glazed facade in office buildings. The primary functions of the solar shading devices are to control solar gains leading to cooling needs during operational hours and reduction of discomfort caused by glare. A secondary property of shading devices incorporated in glazing units is that they can be utilized as an additional layer in the glazing unit when the shading device is deployed. This can improve the thermal transmittance value (U-value) of the windows. It can be deployed during night-time or in periods when a blocked view does not have any consequences for the users of the building. This article presents hot-box measurements of thermal transmittance values (U-values) performed for three insulated glazing units with integrated in-between pane shading systems. The shading devices are venetian-type blinds with horizontal aluminum slats. The windows with double- and triple-pane glazing units have motorized blinds. The window with a 4-pane glazing has a manually operated blind placed in an external coupled cavity.
The measurements are compared to numerical simulations using the WINDOW and THERM simulation tools. The results showed that only minor reductions of U-values of the glazing units were obtained as function of shading system operation. It was, however, found that the introduction of shading devices in the window cavities will increase the total U-value of the window due to thermal bridging effects caused by shading device motor and the aluminium slats of the blinds. coupled cavity.
Abstract
The application of traditional thermal insulation materials requires thicker building envelopes in order to satisfy the requirements of the emerging zero energy and zero emission buildings. This work summarizes the steps from the state-of-theart thermal insulation materials and solutions, like vacuum insulation panels (VIP), gas-filled panels (GFP) and aerogels which all have various drawbacks, to our concepts and experimental investigations for making superinsulation materials (SIM) like e.g. nano insulation materials (NIM).
The adoption of Phase Change Materials (PCMs) in glazing systems was proposed to increase the heat capacity of the fenestration, being some PCMs partially transparent to visible radiation.
The aim of the PCM glazing concept was to let (part) of the visible spectrum of the solar radiation enter the indoor environment, providing daylighting, while absorbing (the largest part of) the infrared radiation.
In this paper, the influence of the PCM glazing configuration is investigated by means of numerical simulations carried out with a validated numerical model. Various triple glazing configurations, where one of the two cavities is filled with a PCM, are simulated, and PCM melting temperatures are investigated. The investigation is carried out in a humid subtropical climate (Cfa according to Köppen climate classifi-cation), and “typical days” for each season are used.
The results show that the position of the PCM layer (inside the outer or the inner cavity) has a relevant influence on the thermo-physical behaviour of the PCM glazing system. PCM glazing systems (especially those with the PCM layer inside the outermost cavity) can be beneficial in terms of thermal comfort. The assessment of the energy performance and efficiency is instead more complex and sometimes controversial. All the configurations are able to reduce the solar gain during the daytime, but sometimes the behaviour of the PCM glazing is less efficient than the reference one.
Pilot projects of sustainable climate-adapted architecture and the national research for carbon neutral buildings